ZT-2026 – Wireless 4-ch Voltage Input

ZT-2026 – Wireless 4-ch Voltage Input

Marcas:

Datasheet, Manual e Outros

Datasheet, Manual e Outros

REF: ZT-2026 Categoria: Tags: , , , ,
  • Descrição
  • Informação adicional
  • Introduction
  • Specifications
  • Ordering information
  • Accessories

Descrição

  • ISM 2.4 GHz Operating Frequency
  • Fully Compliant with 2.4G/ZigBee Specifications
  • Wireless Transmission Range up to 700 m
  • GUI Configuration Software (Windows Version)
  • 4 AI, 2 AO, 2 DI and 2 DO Channels
  • Individual Channel Configuration
  • Overvoltage Protection is up to 240 Vrms
  • Surge and ESD Protection
  • Configurable Power-on Value Settings
  • Configurable Safe Value Settings
  • DIN-Rail Mounting

Informação adicional

Modelos

ZT-2026

The ZT-2026 is a wireless ZigBee module that offers 4 differential analog input channels, 2 analog output channels, 2 digital input channels and 2 digital output channels and provides a programmable analog input and output range. Each analog input channel can be configured to an individual range and each has 240 Vrms overvoltage protection. There are also options for a power-on value and a safe value. Users can easily configure the module address, protocol, checksum, ZT-PID, ZT-channel and type code settings using a combination of rotary and DIP switches.

Communication Interface
Wireless Standards ZigBee 2007 Pro
Transmission Power 11 dBm(FCC Certificated) ( Max 19 dBm)
2.4 GHz Antenna 5 dBi Omni directional
Transmission Range (LoS) 700 m (Typical)
Certification CE/FCC, FCC ID
Max. Slaves in a ZigBee Network 255
ZB-100R/ZB-100T Support -
Protocols Supports DCON and Modbus RTU Protocols
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
Hot Swap Rotary and DIP switch
LED Indicators
Power 1 LED, red
ZigBee Communication 1 LED, green
Isolation
Intra-module Isolated, Field-to-Logic 2500 VDC (for AI, AO, DI and DO)
EMS Protection
ESD (IEC 61000-4-2) 4 kV Contact for Power Line, Communication Line and each Channel, 8 kV Air for Random Point
EFT (IEC 61000-4-4) 4 kV for Power Line
Power
Input Voltage Range +10 VDC ~ +30 VDC (Reverse Polarity Protection)
Power Consumption 2.1 W Max.
Mechanical
Flammability Fire Retardant Materials (UL94-V0 Level)
Dimensions (W x L x H) 33 mm x 87 mm x 107 mm
Installation DIN-Rail
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Relative Humidity 10 ~ 90% RH, Non-condensing

 

Analog Input
Input Channels 4 Differential
Input Types +/-10 V, +/-5 V, +/-1 V, +/-500 mV, +/-150 mV or -20 mA ~ +20 mA (Requires Optional External 125 Ω Resistor)
Resolution 16-bit
Sampling Rate 10 Samples/Second (Total)
Accuracy +/-0.1% of FSR
-3dB Bandwidth 15.7 Hz
Zero Drift +/-20 μV/°C
Span Drift +/-25 ppm/°C
Common Mode Rejectio 86 dB
Normal Mode Rejection 100 dB
Input Impedance >2 MΩ
Overvoltage Protection 240 Vrms
Individual Channel Confi guration Yes
Analog Output
Output Channels 2
Output Types +/-10 VDC, +/-5 VDC, 0 ~ 10 VDC or 0 ~ 5 VDC
Resolution 12-bit
Accuracy +/-0.1% of FSR
Zero Drift +/-30 μV/°C
Span Drift +/-25 ppm/°C
Programmable Output Slope 0.0625 ~ 512 V/Second
Voltage Capability 20 mA @ 10 V
Power-on Value Yes
Safe Value Yes
Digital Input
Input Channels 2 (Sink)
On Voltage Level 3.5 VDC ~ 50 VDC
Off Voltage Level 1 VDC Max.
Input Impedance 10 KΩ
Event Counters Channels : 2
Max. Count: 16-bit (65535)
Max. Input Frequency: 50 Hz
Min. Pulse Width: 10 ms
Digital Output
Output Channels 2 (Sink)
Output Types Isolated Open Collector
Max. Load Current 700 mA/channel
Load Voltage +5 VDC ~ +50 VDC
Short Circuit Protection Yes
Power-on Value Yes
ZT-2026 CR Wireless 4-ch Voltage Input, 2-channle Voltage Output, 2-channle Digital Input and 2-channle Digital Output Module (RoHS)
(Long Range)
Important Note: Zigbee Data Acquisition modules need a Zigbee host converter to coordinate the data transmission route. Please remember to order a ZT-2550, ZT-2570 ZigBee host converter when you purchase Zigbee Data Acquisition products.
MDR-20-24 24 VDC/1.0 A, 24 W Power Supply with DIN-Rail Mounting
ZT-2510 CR ZigBee Repeater (RoHS)
ZT-2550 CR RS-485/RS-232 to ZigBee Converter (Host)
ZT-2570 CR Ethernet/RS-485/RS-232 to ZigBee Converter (Host) (RoHS)
External Antenna 2.4GHz External Antenna, RP SMA Male (Plug)
Extension Cable 3S00x-1, RG58A/U x Meter Long RP-SMA male to RP-SMA Female

Você também pode gostar de…