FLP-12,5 V/3 S

FLP-12,5 V/3 S

Product Documents

Fora de estoque

Categoria Tags: , , ,
  • Descrição
  • Technical specifications

Descrição

pluggable module, visual fault signalling, module locking, remote fault signalling
three-pole varistor lightning current arrester, installation at the boundary of zones LPZ 0 and LPZ 1 or higher, for objects in LPL III and IV, for protection against impact of partial lightning currents, induced overvoltages during a lightning strike or switching overvoltages

Type of SPD 

T1,T2

Nominal voltage 

Un

230

V AC

Maximum operating voltage 

Uc

275,00

V AC

Maximum operating voltage 

Uc

350,00

V DC

Lightning impulse current (10/350 µs) 

Iimp

12,50

kA

Nominal discharge current (8/20 µs) 

In

30,00

kA

Maximum discharge current (8/20 µs) 

Imax

60,00

kA

Voltage protection level at 5 kA 

Up

0,90

kV

Voltage protection level 

Up

1,50

kV

Short-circuit current rating 

ISCCR

50,0

kA

Maximum overcurrent protection 

160 A gL/gG

Response time 

ta

25

ns

TOV 5 s L-N 

335

V

TOV characteristic (TOV 5 s) 

withstand

Cross-section of connected conductors solid (min) 

1,00

mm2

Cross-section of connected conductors solid (max) 

35,00

mm2

Cross-section of connected conductors stranded (min) 

1,00

mm2

Cross-section of connected conductors stranded (max) 

25,00

mm2

Fault indication 

red indication field

Remote indication 

potential-free change-over contact

Remote indication contacts 

250V/0,5A AC,250V/0,1A DC

Cross-section of remote indication conductors 

1,5

mm2

Degree of protection 

IP 20

Range of operating temperatures - min 

-40

°C

Range of operating temperatures - max 

80

°C

Mounting 

DIN rail 35 mm

According to standard 

EN 61643-11:2012, IEC 61643-11:2011

Plug module 

FLP-12,5 V/0

ETIM Class 

EC001457