CAN-2018D – DeviceNet Slave Module of 8-channel thermocouple input

CAN-2018D – DeviceNet Slave Module of 8-channel thermocouple input

Marcas:

Datasheet, Manual e Outros

Datasheet, Manual e Outros

REF: CAN-2018D Categoria: Tags: , , , , , , , , , , ,
  • Descrição
  • Informação adicional
  • Applications
  • Hardware Spec
  • Thermocouple Type
  • Ordering Info
  • Related Products

Descrição

DeviceNet is one kind of the network protocols based on the CAN bus and mainly used for the embedded network of the machine control, such as industrial machine control , aircraft engines monitoring, factory automation, medical equipments control, remote data acquisition, environmental monitoring, and packaging machines control, etc.

The CAN-2018D follows DeviceNet specification Volume I/II, Release 2.0. User can access the thermocouple input status and set the configuration via DeviceNet EDS file. CAN-2018D has 8-channel thermocouple input and it can be used to various applications. By the DeviceNet masters of ICP DAS, you can quickly build a DeviceNet network to approach your requirements. For more information about the DeviceNet master interfaces and other DeviceNet products, please refer to the following web site.

Informação adicional

Modelos

CAN-2018D


DeviceNet Interface
DeviceNet Specification
Volume I, Release 2.0 & Volume II, Release 2.0, Errata5
DeviceNet subscribe
Group 2 Only Server
Connection supported
1 connection for Explicit Messaging
1 connection for Polled I/O
1 connection for Bit-Strobe I/O
Baud Rate Setting by Rotary Switch
125 kbps, 250 kbps, 500 kbps
Node ID Setting by Rotary Switch
0 ~ 63
Heartbeat message
Yes
Shutdown message
Yes
Terminator Resistor
Switch for 120 Ω terminator resistor
Connector
5-pin screwed terminal block
(CAN_GND, CAN_L, CAN_SHLD, CAN_H, CAN_V+)
EDS file
Yes
Analog Input
Channels
8
Input Type
+/- 15mV, +/- 50mV, +/- 100mV, +/- 500mV, +/- 1V, +/- 2.5V
+/-20mA,(Requires Optional External 125 Ohm Resistor)
Thermocouple (J, K, T, E, R, S, B, N, C)
Resolution
16-bit
Sampling Rate
10 Samples/Sec. (Total)
Accuracy
+/-0.1% FSR
Zero Drift
+/- 10 μV/ °C
Span Drift
+/- 25 ppm/ °C
Common Mode Rejection
86 dB
Normal Mode Rejection
100 dB
Input Impedance
>400 kΩ
Individual Channel Configuration
Yes
Open Thermocouple Detection
Yes
Over voltage Protection
240 Vrms
ESD Protection
+/-4kV, Contact for each terminal.
Intra-module Isolation, Field to Logic
3000 VDC
LED
Power
PWR, red
DeviceNet Status
NET/MOD, green/orange
Power
Power Supply
Unregulated +10 ~ +30 VDC
Power Consumption
1.5 W
Mechanism
Installation
DIN-Rail
Dimensions
33 mm x 99 mm x 78 mm (W x L x H)
Environment
Operating Temp.
-25 ~ 75 ℃
Storage Temp.
-30 ~ 80 ℃
Humidity
10 ~ 90% RH, non-condensing
Type Code
Temperature Range (°C)
J
-210 °C ~ +1200 °C
K
-270 °C ~ +1372 °C
T
-270 °C ~ +400 °C
E
-270 °C ~ +1000 °C
R
-50 °C ~ +1765 °C
S
-50 °C ~ +1765 °C
B
0 °C ~ +1820 °C
N
-270 °C ~ +1300 °C
C
0 °C ~ +2320 °C
CAN-2018D
DeviceNet Slave Module of 8-channel Thermocouple Input
Include CAN-2018D module and a CN-1824 daughter board
DeivceNet Master Library Support PISO-CAN serials, PEX-CAN serials and PCM-CAN with DeviceNet master library
PISO-DNM100U-D
PISO-DNM100U-T
1 Port Intelligent DeviceNet Master Communication Board with DeviceNet Firmware Inside for universal PCI bus
I-7565-DNM-G CR USB/DeviceNet Master communication Converter with D-sub 9-pin connector
I-8124W 1 Port DeviceNet Master Module with dual port RAM
I-87124 1 Port High Performance DeviceNet Master Module
CA-0910-C 9-pin Female D-sub & 3-wire CAN bus cable (1M)