Atualizando informações ...

U-7550M Módulo OPC UA com 12 DI 6 DO 2 Ethernet Switch Alta Performance ICP Das

Ref: U-7550AM CR
Marca: ICP Das
Modelo: U-7550AM CR

Área: Aquisição de Dados  
Característica: OPC UA  
Interface: Ethernet  

Não disponível

Enviar
Avise-me quando estiver disponível
Descrição
U-7550M Módulo OPC UA com 12 DI 6 DO 2 Ethernet Switch Alta Performance ICP Das
Características
  • Ãrea: Aquisição de Dados
  • Característica: OPC UA
  • Interface: Ethernet
Avaliações
Mais Informações

Software
Protocol • OPC UA Server / Client
• MQTT Client
• RESTful API
Function • Web Interface for Configuration
• Scaling
• Security
• Rule Setting
• Schedule
• Event Log
• IoTstar Setting
CPU Module
CPU 32-bit CPU (400 MHz)
Watchdog Timer Module, Communication (Programmable)
Isolation
2-way Isolation I/O: 2500 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for each terminal
±8 kV Air for random point
LED Indicators
Status Run, Ethernet, I/O
Digital Input/Counter
Channels 12
Type Dry Contact, Wet Contact
Sink/Source (NPN/PNP) Dry: Source
Wet: Sink
ON Voltage Level Dry: Close to GND
Wet: 1 VDC (max.)
OFF Voltage Level Dry: Open
Wet: +3.5 ~ +50 VDC (max.)
Max. Counts 4,294,967,295 (32-bit)
Frequency 100 Hz
Min. Pulse Width 5 ms
Input Impedance 10 kΩ
Overvoltage Protection +60 VDC
Digital Output
Channels 6
Type Isolated Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +5 ~ +50 VDC
Load Current 500 mA/channel
Overvoltage Protection +60 VDC
Overload Protection 1.3 A
Short-circuit Protection Yes
Power on Value Programmable
Safe Value Programmable
Ethernet
Ports 2 x RJ-45, 10/100 Base-TX, Swtich Ports
PoE Yes
LAN bypass Yes
Security ID, Password and IP Filter
Power
Reverse Polarity Protection Yes
Consumption 2.9 W
Powered from PoE IEEE 802.3af, Class2
Powered from Terminal Block +12 ~ +48 VDC
Mechanical
Dimensions (mm) 97 x 120 x 47 (W x L x H)
Installation DIN-Rail mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing

Produtos visualizados