MP-6000R8 – 24 V/25 A, 600W Output Modularized Redundant Power for DCS system

MP-6000R8 – 24 V/25 A, 600W Output Modularized Redundant Power for DCS system

Marcas:

REF: MP-6000R8 Categoria: Tags: , , ,
  • Descrição
  • Informação adicional
  • Features
  • Specifications
  • Ordering information

Descrição

24 V/25 A, 600W Output Modularized Redundant Power for DCS system

Informação adicional

Modelos

MP-6000R8

  • Wide input voltage 90 to 264 VAC, 47 to 63Hz
  • Internal EMI filter
  • Input surge current and overload protection
  • Overvoltage protection
  • Built-in active PFC function, PF > 0.95
  • Power lose detection
Output
DC Voltage 24 VDC (with the range of 23.7 ~ 25.2 VDC)
Rated Current 25 A
Ripple & Noise 240mVp-p
Voltage Tolerance 5%
Line Regulation 1%
Load Regulation 5%
Setup/Rise Time 3 second max.
Hold Up Time 70ms, 110 VAC
130ms, 230 VAC
Input
Voltage Range 90 ~ 264 VAC
Frequency Range 47 ~ 63 Hz
Power Factor > 0.95
Efficiency 83%
Inrush Current 60A
Leakage Current 6mA
Protection
Overload Overload at the output will not cause damage the power supply; the output will auto recovery at once after removing the circuit while setting at 110% to 150% of the maximum load.
Over Voltage Overvoltage protection is available on output, if the output voltage reaches an overvoltage condition shall be set at 112% to 132% for its protecting point and then the output will auto recovery at once after removing the abnormal circuit.
Function
Power lose detection When the Power system working, it’s open between terminal D and I.
When AC power failure, it’s short between terminal D and I.
When one of the power when an exception occurs, it’s short between terminal D and I.
Environmental
Working Temperature -20 ~ +35°C
Working Humidity 5 ~ 95% RH, Non-condensing
Safety & EMC
Safety Standards C.S.A C22.2, EN60950-1
Withstand Voltage I/P-O/P: 4KVDC, I/P-FG: 2KVDC
Isolation Resistance I/P-O/P, I/P-FG, O/P-FG:>50M Ohms / 500VDC
EMC Emission EN55022 (CISPR22) Class A, EN61000-3-2,-3
EMC Immunity EN61000-4-2 ~ 6, EN61000-4-8, EN61000-4-11, EN55024
Others
MTBF MTBF(theoretical) at 25°C ambient temp and half load, according to MIL-217F:100,000hrs above.
Lifetime > 8 year at 24 hours in function at load of 1.5A.
Dimension (W x H x D) 178 x 437.2 x 229.4 mm
MP-6000R8 24 V/25 A, 600W Output Modularized Redundant Power for DCS system