FR-2156T – The FR-2156T has 8-channels isolated photo-coupler output

FR-2156T – The FR-2156T has 8-channels isolated photo-coupler output

Marcas:

Datasheet, Manual e Outros

Datasheet, Manual e Outros

REF: FR-2156T Categoria: Tags: , , , ,
  • Descrição
  • Informação adicional
  • Features
  • Applications
  • Specifications
  • Ordering Info

Descrição

The FR-2156T has 8-channels isolated photo-coupler output and the transfer speed is fixed at 1M bps. The default signal connector of FR-2156T is a 12-pin 0.15” screw terminal connector.According to different applications, the users can choose suitable modules. The FR-2100 I/O module has a FRNet interface. The users can daisy chain several FR-2100 modules together. Via FRNet, the FR-2100 modules can extend the discrete I/O control of PC and PAC easily. For further information about the networking of FR-2100 series; please refer to literature related to I-7188EF, I-8172, FRB-200

Informação adicional

Modelos

FR-2156T

Built-in Wire-saving FRnet DI/DO control
High-speed transmission reliability
Simple synchronization mechanism
No software overhead on protocol processing
Supporting broadcasting (1:n data transmission)
Duplicating output easily
Fixed I/O scan-time and I/O synchronization
DIN-Rail mountable
Industrial Automation
Remote I/O control
Wire-saving application
Built-in Wire-saving FRnet DI/DO control
6P4C RJ-11 modular connector with Cat.3 cable (2P twisted-pair cable) for easy wiring( When different cables are used, the transmission distance may change).
Power consumption 2.0 W (Max.)
Power requirement 12-24 V DC
Operating temperature -25°C to +65 °C
Operating humidity 10% ~ 95% RH, non-condensing
Storage temperature -30°C to +85°C
Storage humidity 5% ~ 95% RH, non-condensing
Weight approximately 120g
Dimensions 99 mm x 32 mm x 83 mm
Output Isolation 1 KVdc
Output type 4.7 K Ohm
Output points 8 channels
Sink Current 300mA per channel max.
Response Time Turn-On delay time: less than 0.15 ms
Turn-Off delay time: less than 0.05 ms
Output Protection Thermal shutdown with auto restart
Overload protection
Short circuit protection
Over-voltage protection
Current limitation.
Transmission Transfer speed:1 M bps
Cyclic scan time:0.72 ms
Transfer distance:Max. 100 m
FR-2156T    8-channel isolated digital output with 12- pin screw terminal connector